ICAR Automatic Power Factor FH 20 Detuned

ICAR Automatic Power Factor FH 20 Detuned

Qty:
Brand:
Make An Enquiry

Description

ICAR Automatic Power Factor FH 20 Detuned
Detuned fix PFC system
MICROfix
Ue UN UMAX* f THDIR% I
250Hz%** THDVR% fD
400-415V 550V 600V 50Hz 100% ≤25% ≤6% 180Hz
* Maximum admissible value according to IEC 60831-1.
** Percent current of 5th harmonic.
Technical characteristics
Rated operational voltage Ue=400-415V
Rated frequency 50Hz
Max current overload In (bank) 1,3 In
Max current overload In
(capacitors @40°C)
1,3 In (continuous)
2 In (x380s every 60 minutes)
3 In (x150s every 60 minutes)
4 In (x70s every 60 minutes)
5 In (x45s every 60 minutes)
Max overload Vn (bank) 1,1xUe
Max overload Vn (capacitors) 3xUN (for 1 minute)
Insulation voltage 690V
Temperature class (bank) -5/+40°C
Temperature class (capacitors) -25/+55°C
Discharge device mounted on each bank
Installation indoor
Service continuous
Internal connection delta
Total losses ~ 6W/kvar
Inner surface finish zinc passivation
Standards (bank) IEC 61439-1/2, IEC 61921
Standards (capacitors) IEC 60831-1/2
Generalities of ICAR Automatic Power Factor FH 20 Detuned:
• Zink-passivated metallic enclosure painted with epossidic
dust paint, colour RAL 7035.
• Load-break switch with door interlock.
• Fuses with high breaking power NH00-gG.
• FS17 450/750V self-extinguish cable according to EN
50525 – EN 50575 – EN 50575/A1.
• IP3X protection degree.
• CRM25 single phase self-healing metallized polypropylene
capacitor with UN=550V rated voltage.
• Discharge resistance.
• Three phase detuning choke with tuning frequency
fD=180Hz (N=3.6-p%=7.7%).

Additional information

Power at 415V

278 kvar, 321 kvar, 450 knar, 535 kvar, 770 kvar

Reviews

There are no reviews yet.

Be the first to review “ICAR Automatic Power Factor FH 20 Detuned”

ICAR data sheet

Download
X